44521 Hastings Drive (ACC5)
44521 Hastings Drive, Ashburn, VA, 20147, US
ACC5 at 44521 Hastings Drive in Ashburn was described by its developer as the prototype for its ground-up projects, on the strength of its power capacity and flexible design. It carries 36.4 MW of critical load within a total electrical load of 59.6 MW, fed at 34.5 kV from two separate points into sixteen 5 MVA pad-mount transformers, across 176,000 sq ft of raised floor in a 360,000 sq ft building. The cooling plant is built for scale: sixteen chillers, sixteen cooling towers, roughly 480 CRAH units and half a million gallons of chilled-water thermal storage across two cross-connected plants. The LINX NoVA internet exchange node was built in this building, and the site holds Open-IX certification alongside LEED Gold.
Facility Specifications
Site information
- Colocation space
- 176,000 sq ft of raised floor within a 360,000 sq ft building
- Power capacity
- 36.4 MW critical load within 59.6 MW total electrical load; 34.5 kV service from two separate points into sixteen 5 MVA pad-mount transformers; rotary UPS with 2,500 kW generators; two 50,000-gallon underground fuel stores
Power & cooling
- Redundancy
- UPS N+1; cooling N+1
- Cooling
- Sixteen chillers, sixteen cooling towers and roughly 480 CRAH units across two cross-connected plants; 500,000 gallons of chilled-water thermal storage; reclaimed-water evaporative chilling
Compliance
Platforms & amenities
- Platforms & services
- Wholesale data centre space with Open-IX certified interconnection; cross-connects within the Ashburn Corporate Campus and to the wider Loudoun fibre network
- Amenities
- The building LINX chose for its Northern Virginia exchange node
Network ecosystem — 6 carriers on-net
Notable: Cogent Communications, Inc. (AS174)